Eaton / Cutler Hammer QCGFEP1020 QuickLag® Cable In Cable Out Ground Fault Miniature Circuit Breaker; 20 Amp, 120 Volt AC, 1-Pole

*Images are representative of products listed and may not be actual product.

     

AVAILABILITY

Ready to Ship
0


Need more? Additional inventory ships in 10 business days.


Out of stock.
Ships in 10 business days.


Add to Shopping List

Your Price
$440.26 / each


 
Vendor: Eaton / Cutler Hammer
Cat #: QCGFEP1020
Part #: 35166
SKU: 42914
UPC #: 786679146552

Product Details

Dimension: 1.300 Inch Width x 3.300 Inch Depth x 5.200 Inch Height
30 Milli-Amp of trip sensitivity
Single-throw double-pole contacts are UL and CSA listed for 5 Amperes at 250 Volt AC
Bell alarm (W1) - contacts change state when breaker trips
Auxiliary switch (W2) - contacts change state when breaker is opened (or tripped) or closed
14 Inch long 18 AWG pigtail wire leads provided
Line terminal extended tangs which bolt directly to the bus

Eaton Quicklag & reg Miniature circuit breaker for ground fault equipment protection measures 1.3 Inch x 3.3 Inch x 5.2 Inch and comes in cable in/cable out configuration that offers wide variety of mounting styles available to install in many different applications. It has voltage rating of 120 VAC, current rating of 20 Amps at 40 deg C and trip sensitivity of 30 milli-Amps. It offers interrupting capacity of 10000 Amps at 120 VAC. Circuit breaker is provided with ring line terminal/box lug load terminal type for quick fastening and permits terminal wires of size 14 - 10 AWG and 14 - 4 AWG. It is UL listed and CSA certified.

Product Specifications

Amperage Rating 20 Amp
Application For Industrial, Residential Use
Catalog Description Quicklag Industrial Ground Fault Thermal-Magnetic Equipment Protector, Single-pole, 30 mA Trip Sensitivity, 20A, 10 kAIC, 120V
Catalog Number QCGFEP1020
Circuit Breaker Type QCGF
Connection Cable-in/Cable-out
Country of Origin DO
Dimension 1.300 Inch Width x 3.300 Inch Depth x 5.200 Inch Height
EU RoHS Indicator C
GTIN 00786679146552
Gross Weight 0.550
Height 1.3
Interrupt Rating 10 Kilo-Amp
Invoice Description English Quicklag Industrial Ground Fault Thermal-Magnetic Equipment Protector
Item Miniature Circuit Breaker
Length 5.2
Mfr/Vendor Eaton / Cutler Hammer
Number Of Poles 1
Number of Poles 1
Select Code DISTRIBUTION EQUIP
ShortDescriptionStripped Eaton-Cutler-Hammer-QCGFEP1020-QuickLag-Cable-In
Special Features 30 mA Trip Sensitivity
Standard UL Listed; CSA Certified
Standards UL 943
Sub Brand QuickLag®
Temperature Rating 40 deg C
Trip Type Non-Interchangeable, Thermal-Magnetic
Type Cable-In/Cable-Out, Ground Fault
UPC 786679146552
Voltage Rating 120 Volt AC
Weight 0.550
Width 3.3
Wire Size 18 AWG Pigtail
description ETN QCGFEP1020 Quicklag Industrial
feature#1 Dimension: 1.300 Inch Width x 3.300 Inch Depth x 5.200 Inch Height
feature#2 Dimension: 1.460 Inch Length x 1.180 Inch Width x 2.220 Inch Height
feature#3 Single-throw double-pole contacts are UL and CSA listed for 5 Amperes at 250 Volt AC
feature#4 Bell alarm (W1) - contacts change state when breaker trips
feature#5 Auxiliary switch (W2) - contacts change state when breaker is opened (or tripped) or closed
feature#6 14 Inch long 18 AWG pigtail wire leads provided
feature#7 Line terminal extended tangs which bolt directly to the bus