Schneider Electric / Square D S29390 Powerpact® Shunt Trip; 24 Volt DC

*Images are representative of products listed and may not be actual product.

     

AVAILABILITY

Ready to Ship
30


Need more? Additional inventory ships in 10 business days.


Add to Shopping List

Your Price
$588.18 / each


 
Vendor: Square D by Schneider Electric
Cat #: S29390
Part #: 38671
SKU: 424079
UPC #: 785901627579

Product Details

Trips the circuit breaker when the control voltage rises above 70% of its rated voltage
Tripping by the shunt trip or underVoltage trip has priority over manual (or motor operator) closing, in the presence of a standing trip order such an action does not result in any closing, even temporarily, of the main contacts
The circuit breaker must be reset locally after being tripped by shunt trip (MX)
AC shunt trips are suitable for ground-fault protection when combined with a Class I ground-fault sensing element
Impulse type 20 ms or maintained control signals
Endurance is 50% of the rated mechanical endurance of the circuit breaker
Clearing time- Less Than 50 ms
A voltage release can be used to trip the circuit breaker using a control signal

Schneider Electric / Square D Powerpact® Standard Electric Circuit breaker shunt trip has voltage rating of 24 VDC and power rating of 5 Watts. It has conductor size of 18 to 14 AWG. Circuit breaker is equipped with a unique snap-in terminal design that makes converting between busbar and lug options easy. It is easy to install, extremely versatile and includes a wide variety of terminal options like mechanical lugs, crimp lugs, power distribution lugs and lug shields. It has applications on construction, commercial buildings, oil & gas,control equipment panels, marine, industrial buildings, water wastewater, OEM commercial, healthcare facilities, data centers, educational campuses and industrial markets. Circuit breaker is UL 489 Listed, CSA, NEMA, NMX, VDE, BS, CCC, IEC certified and CE marked for global acceptance.

Product Specifications

Application For Use On H, J And L-Frame Circuit Breakers
Catalog Description CIRCUIT BREAKER SHUNT TRIP 24V DC
Catalog Number S29390
Commodity Code 32900
Connection Terminal
Country of Origin FR
DC Voltage Rating 24 Vdc
EU RoHS Indicator Y
GTIN 00785901627579
Gross Weight 0.280
In Stock Yes
Invoice Description English CIRCUIT BREAKER SHUNT TRIP 24V DC
Item Shunt Trip
Mfr/Vendor Square D by Schneider Electric
Power Rating 5 Watt
Select Code DISTRIBUTION EQUIP
ShortDescriptionStripped Schneider-Electric-Square-D-S29390-Powerpact-Shunt
Standards UL Listed, IEC Rated
Sub Brand Powerpact®
Type Type MX, Standard
UPC 785901627579
Used On Powerpact D/H/J Frame Circuit Breaker
Voltage Rating 24 Volt DC
Wire Size 18-14 AWG Stranded (Copper)
description SQD S29390 CIRCUIT BREAKER SHUNT TR
feature#1 Trips the circuit breaker when the control voltage rises above 70% of its rated voltage
feature#2 Dimension: 1.460 Inch Length x 1.180 Inch Width x 2.220 Inch Height
feature#3 The circuit breaker must be reset locally after being tripped by shunt trip (MX)
feature#4 AC shunt trips are suitable for ground-fault protection when combined with a Class I ground-fault sensing element
feature#5 Impulse type 20 ms or maintained control signals
feature#6 Endurance is 50% of the rated mechanical endurance of the circuit breaker
feature#7 Clearing time- Less Than 50 ms
feature#8 A voltage release can be used to trip the circuit breaker using a control signal