ABB A40-30-01-81 Non-Reversing AC operated IEC Contactor; 3-Pole, 3 Phase, 60 Amp At 40/55 deg C 690 Volt, 42 Amp At 70 deg C 690 Volt, 24 Volt Coil At 50/60 Hz, DIN-Rail/Common Base Plate Mount

*Images are representative of products listed and may not be actual product.
  • ABB A40-30-01-81 ABB A40-30-01-81 Non-Reversing AC operated IEC Contactor; 3-Pole, 3 Phase, 60 Amp At 40/55 deg C 690 Volt, 42 Amp At 70 deg C 690 Volt, 24 Volt Coil At 50/60 Hz, DIN-Rail/Common Base Plate Mount
Manufacturer: ABB
Catalog#: A40-30-01-81
Crescent Part#: 302
UPC: 662019653808
Your Price:

Product Details

Size: 101 mm Length x 115 mm Width x 61 mm Height

Laminated magnetic coil circuit

E16DU and TA25DU overload relays are used

Product Details:

ABB 3-Pole 3-Phase Non-reversing AC operated IEC contactor features touch safe design for comfort. It offers easy maintenance of contacts and coil inspection. Contactor resists impulse voltage of 8 kilo-Volts. It measures 101 mm x 115 mm x 61 mm. Contactor is designed for controlling motors and power circuits up to 690 VAC or 220 VDC. It has power rating of 11 kilo-Watts at 220/230/240 Volts, 18.5 kilo-Watts at 380/400/415 Volts and 22 kilo-Watts at 440/500/690 Volts. It has voltage rating of 110 Volts at 50 Hz/110 - 120 Volts at 60 Hz and a current rating of 60 Amps at 40/55 deg C 690 Volts/42 Amps at 70 deg C 690 Volts/70 Amps at 70 deg C 690 Volts.

Contactor has a power rating of 10 hp at 208 Volts/15 hp at 240 Volts/30 hp at 480 Volts and 40 hp at 575/600 Volts. It has a main wires of size 6 AWG - 250 KCMIL and auxiliary wires of size 18 - 14 AWG. Contactor has screw terminal connection for easy installation. It has a coil voltage of 24 Volts at 50/60 Hz. It finds its applications in isolation, capacitor switching and lighting. CSA Certified contactor is UL listed and meets RoHS complaint.

Product Specification

Product Details
Manufacturer ABB
Catalog# A40-30-01-81
Shipping Information
Ships Ground. Eligible for expedited shipping Yes
Other Information
Motor Power 10 hp at 208 Volt, 15 hp at 240 Volt, 30 hp at 480 Volt, 40 hp at 575/600 Volt
Mounting DIN-Rail/Common Base Plate
Maximum Breaking Capacity 2500 Amp At 690 Volt, 3000 Amp At 440 Volt
Item Non-Reversing Contactor
Connection Screw Terminal
Degree Of Protection IP00 (Main Terminals), IP20 (Coil Terminals)
Contact Configuration 3 NO Main, 1 NC Auxiliary
Dielectric Voltage 1000 Volt (IEC 60947-4-1), 600 Volt (UL/CSA)
Environmental Conditions Maximum Operating Altitude Permissible 3000 m, -60 to 80 deg C Storage Temperature
Brand Name ABB
Coil Voltage 24 Volt AC at 50/60 Hz
Power Rating 11 kilowatt At 220/230/240 Volt, 18.5 kilowatt At 380/400/415 Volt, 22 kilowatt At 440/500/690 Volt
Phase 3
Operating Cycles 5 Million Mechanical Cycle
Number Of Poles 3
Size 101 mm Width x 115 mm Depth x 61 mm Height
Application For Controlling 3-Phase Motors And Generally For Controlling Power Circuits Up To 690 Volt AC Or 220 Volt DC And For Contactors, Can Also Be Used For Many Other Applications Such As Isolation, Capacitor Switching, Lighting
Amperage Rating 60 Amp at 40/55 deg C 690 Volt, 42 Amp at 70 deg C 690 Volt
Frequency Rating 50/60 Hz
Frame A40
Wire Size 6 AWG - 250 KCMIL Main, 18-14 AWG Auxiliary
Voltage Rating 110 Volt At 50 Hz, 110 - 120 Volt At 60 Hz
Type AC Operated
Torque Range 240 Inch-lb
Temperature Rating -25 to 55 deg C Fitted With Thermal Overload Relay, -40 to 70 deg C Without Thermal Overload Relay
Standards UL Listed, CSA Certified, CE, BV, CCC, DNV, GL, GOST, LR, RINA, RMRS Certified, RoHS Complaint