Ericson 1075-MR Manual Power Up GFCI Module; 2400 Watt, 20 Amp, Lighted NEON, Panel Mount

*Images are representative of products listed and may not be actual product.
  • Ericson 1075-MR Ericson 1075-MR Manual Power Up GFCI Module; 2400 Watt, 20 Amp, Lighted NEON, Panel Mount
Manufacturer: Ericson
Catalog#: 1075-MR
Crescent Part#: 169349
UPC: 782862490914
Your Price:

Product Details

Size: 2.580 Inch Width x 1.750 Inch Depth x 3.810 Inch Height

Quick and easy field installation into temporary panels and workboxes

Compact and portable, this unit is easy to use, store and transport

Works on two or three wire circuits

Test and reset buttons are clearly marked for easy identification and each is protected from accidental activation

Low voltage let go: 40% rated voltage, lighted NEON indicator

Grounded neutral detection: 2 ohms or less

Radio frequency noise susceptibility: operates normally with 0.5 VRMS, 10-450Mhz, injected on power lines

Product Details:

Ericson Manual power up GFCI module for panel mount has an UV rated polycarbonate enclosure that prevents corrosion and impact. It has a current rating of 20 Amps, voltage rating of 120 Volts and power rating of 2400 Watts. It has an operating temperature of -35 to 66 deg C. Module trips at a level of 4 - 6 milli-Amps and has a trip time of 0.025 second. It has a frequency of 50/60 Hz. It has UL94/5V flammability rating to withstand hazardous environments.

Module measures 2.580 Inch x 1.750 Inch x 3.810 Inch. It is compact/portable and is easy to install. It withstands tough jobsite conditions. Test and reset buttons are clearly marked for quick identification and is protected from accidental activation. High intensity neon indicator lamp glows bright when power is on for easy identification of power status. Box meets cUL/UL/OSHA standards.

Product Specification

Product Details
Manufacturer Ericson
Catalog# 1075-MR
Product Dimensions & Details
Dimensions W:3'' x H:4''
Height 4.00
Width 3.00
Shipping Information
Ships Ground. Eligible for expedited shipping Yes
Other Information
Amperage Rating 20 Amp, 4 - 6 Milli-Amp Trip, 120 Amp Overload
Color Black
Brand Name Ericson
Item Manual Power Up GFCI Module
Material UV Rated Polycarbonate
Mounting Panel
Dimension 2.580 Inch Width x 3.810 Inch Height x 1.750 Inch Depth
Dielectric Strength 1500 Volt RMS Between Line And Load, 2500 Volt RMS Between Current Carrying Conductors And Ground Conductor, 4000 Volt RMS Between Current Carrying Conductors And Enclosure
Environmental Conditions Flammability Rated UL94-5V, 93% Relative Humidity
Frequency Rating 50/60 Hz
Temperature Rating -35 to 66 deg C
Standards UL & cUL Listed to UL943 - 2003, Meets OSHA
Voltage Rating 120 Volt, 6 Kilo-Volt Impulse Surge Withstand
Wattage 2400 Watt

Customer Questions & Answers